North American power transmission grid

From Wikipedia, the free encyclopedia
The two major and three minor North American Electric Reliability Corporation (NERC) interconnections, and the nine NERC Regional Reliability Councils.
The electric power transmission grid of the contiguous United States consists of 120,000 miles (190,000 km) of lines operated by 500 companies.

The electrical power grid that powers Northern America is not a single grid, but is instead divided into multiple wide area synchronous grids.[1] The Eastern Interconnection and the Western Interconnection are the largest. Three other regions include the Texas Interconnection, the Quebec Interconnection, and the Alaska Interconnection. Each region delivers power at a nominal 60 Hz frequency. The regions are not usually directly connected or synchronized to each other, but there are some HVDC Interconnectors.

In the United States[2] and Canada,[3] national standards specify that the nominal voltage supplied to the consumer should be 120 V and allow a range of 114 V to 126 V (RMS) (−5% to +5%). Historically 110 V, 115 V, and 117 V have been used at different times and places in North America.[citation needed] Mains power is sometimes spoken of as 110 V; however, 120 V is the nominal voltage.

History[]

In the United States in the 1920s, utilities formed joint operations to share peak load coverage and backup power. In 1934, with the passage of the Public Utility Holding Company Act (United States), electric utilities were recognized as public goods of importance and were given outlined restrictions and regulatory oversight of their operations.

From 1967, the East and West interconnections were directly connected together. However, the AC ties did not have high capacity and were subject to oscillations, and so their connection proved unreliable. In 1975 the AC ties were disconnected, because DC ties were found to work more reliably.[1]

The Energy Policy Act of 1992 required transmission line owners to allow electric generation companies open access to their network[4][5] and led to a restructuring of how the electric industry operated in an effort to create competition in power generation. No longer were electric utilities built as vertical monopolies, where generation, transmission and distribution were handled by a single company. Now, the three stages could be split among various companies, in an effort to provide fair accessibility to high voltage transmission.[6]: 21 The Energy Policy Act of 2005 allowed incentives and loan guarantees for alternative energy production and to advance innovative technologies that avoided greenhouse emissions.

Attacks by foreign countries[]

In 2009, The Wall Street Journal reported that spies from China and Russia, as well as from other countries, "penetrated the U.S. electrical grid and left behind software programs that could be used to disrupt the system." According to U.S. officials, the spies did not seek to damage the power grid; however they might be able to do so during a war or crisis. Most of the intrusions were detected by American intelligence agencies.[7]

Description[]

There are two major wide area synchronous grids in North America, the Eastern Interconnection and the Western Interconnection. Besides this there are two minor power grids in the U.S., the Alaska Interconnection and the Texas Interconnection. The Eastern, Western and Texas Interconnections are tied together at various points with DC interconnects allowing electrical power to be transmitted throughout the contiguous U.S., Canada and parts of Mexico. The transmission grids are operated by transmission system operators (TSOs), not-for profit companies that are typically owned by the utilities in their respective service areas, where they coordinate, control and monitor the operation of the electrical power system. TSOs are obliged to provide nondiscriminatory transmission access to electricity generators and customers. TSOs can be of two types: Independent System Operators (ISOs) and Regional Transmission Organizations (RTOs). The former operate within a single state, and the latter cover wider areas crossing state borders.[citation needed]

In 2009 there were four RTOs in the U.S.:[citation needed]

There are also three ISOs:

RTOs are similar but not identical to the nine associated in the North American Electric Reliability Corporation (NERC), a nonprofit entity that is in charge of improving the reliability and security of the bulk power system in the U.S., Canada and the northern part of Baja California in Mexico. The members of the Regional Reliability Councils include private, public and cooperative utilities, power marketers and final customers. The Regional Reliability Councils are:

The FERC distinguishes between 10 power markets in the U.S., including the seven for which RTOs have been established, as well as:

  • Northwest
  • Southwest (covering Arizona, most of New Mexico and Colorado)
  • Southeast[8]

ISOs and RTOs were established in the 1990s, when states and regions established wholesale competition for electricity.

North American Electric Reliability Corporation[]

The North American Electric Reliability Corporation (NERC) is a nonprofit corporation based in Atlanta, Georgia, and formed on March 28, 2006, as the successor to the National Electric Reliability Council (also known as NERC), which formed in the wake of the first large-scale blackout in November of 1965. The original NERC was formed on June 1, 1968, by the electric utility industry to promote the reliability and adequacy of bulk power transmission in the electric utility systems of North America. NERC's mission is to "ensure the reliability of the North American bulk power system."[9]

NERC oversees eight regional reliability entities and encompasses all of the interconnected power systems of the contiguous United States, Canada and a portion of Baja California in Mexico.

NERC's major responsibilities include working with all stakeholders to develop standards for power system operation, monitoring and enforcing compliance with those standards, assessing resource adequacy, and providing educational and training resources as part of an accreditation program to ensure power system operators remain qualified and proficient. NERC also investigates and analyzes the causes of significant power system disturbances in order to help prevent future events.

Interconnections[]

Eastern Interconnection[]

The Eastern Interconnection is one of the two major alternating-current (AC) electrical grids in North America.

All of the electric utilities in the Eastern Interconnection are electrically tied together during normal system conditions and operate at a synchronized frequency operating at an average of 60 Hz. The Eastern Interconnection reaches from Central Canada eastward to the Atlantic coast (excluding Quebec), south to Florida, and back west to the foot of the Rockies (excluding most of Texas).

Interconnections can be tied to each other via high-voltage direct current power transmission lines (DC ties), or with variable-frequency transformers (VFTs), which permit a controlled flow of energy while also functionally isolating the independent AC frequencies of each side. The Eastern Interconnection is tied to the Western Interconnection with six DC ties, to the Texas Interconnection with two DC ties, and to the Quebec Interconnection with four DC ties and a VFT.

On October 17, 2009, the Tres Amigas SuperStation was announced to connect the Eastern, Western and Texas Interconnections via three 5 GW superconductor links.[10]

Western Interconnection[]

The Western Interconnection is the other major alternating current (AC) power grid in North America.

All of the electric utilities in the Western Interconnection are electrically tied together during normal system conditions and operate at a synchronized frequency of 60 Hz. The Western Interconnection stretches from Western Canada south to Baja California in Mexico, reaching eastward over the Rockies to the Great Plains.

Interconnections can be tied to each other via high-voltage direct current power transmission lines (DC ties) such as the north-south Pacific DC Intertie, or with variable-frequency transformers (VFTs), which permit a controlled flow of energy while also functionally isolating the independent AC frequencies of each side. There are seven DC ties (ca. 200 MW each) to the Eastern Interconnection in the US[11][12] and one in Canada. There are proposals to add four additional HVDC ties.[13] It is not tied to the Alaska Interconnection.

On October 13, 2009, the Tres Amigas SuperStation was announced to connect the Eastern, Western and Texas Interconnections via three 5 GW superconductor links.[10]

Texas Interconnection[]

The Texas Interconnection is one of the three minor alternating current (AC) power grids in North America.

All of the electric utilities in the Texas Interconnection are electrically tied together during normal system conditions, and they operate at a synchronized frequency operating at an average of 60 Hz. The Texas Interconnection covers most of the state of Texas.

Interconnections can be tied to each other via high-voltage direct current power transmission lines (DC ties), or with variable-frequency transformers (VFTs), which permit a controlled flow of energy while also functionally isolating the independent AC frequencies of each side. The Texas Interconnection is tied to the Eastern Interconnection with two DC ties, and has a DC tie and a VFT to non-NERC systems in Mexico. There is one AC tie switch in Dayton, Texas that has been used only one time in its history (after Hurricane Ike).

On October 13, 2009, the Tres Amigas SuperStation was announced to connect the Eastern, Western and Texas Interconnections via three 5 GW superconductor links.[10]

Quebec Interconnection[]

The Québec Interconnection is one of the three minor alternating-current (AC) electrical grids in North America.

The Quebec Interconnection covers all of the Province of Quebec and operates at an average system frequency of 60 Hz. It connects 18 systems in the US and Canada to one electric utility company: Hydro-Québec. It is operated as an independent AC grid for physical reasons.[14] Because of its unique status, it is often[when?] functionally considered[by whom?] part of the Eastern Interconnection.[citation needed]

The Quebec Interconnection is tied to the Eastern Interconnection with four high-voltage direct current power transmission lines (DC ties), and with one variable-frequency transformers (VFTs) line, which isolate the unsynchronized AC frequencies of each side.

Alaska Interconnection[]

The Alaska Interconnection is one of the three minor alternating-current (AC) electrical grids in North America.

It is composed of two grids isolated from each other and from the rest of North American grids.

Proposed improvements[]

Thirty-seven states plus the District of Columbia took some action to modernize electric grids in the first quarter of 2017, according to the North Carolina Clean Energy Technology Center. The states did so to make electricity systems "more resilient and interactive". The most common actions that states took were "advanced metering infrastructure deployment" (19 states did this), smart grid deployment and "time-varying rates for residential customers".[15]

Legislatively, in the first quarter of the year 82 relevant bills were introduced in different parts of the United States. At the close of the quarter, most of the bills remained pending. For example, legislators in Hawaii introduced a bill that would create an energy storage tax credit. In California, the state Senate had a bill that would "create a new energy storage rebate program".[15]

In August 2018, Advanced Energy Economy (AEE) and Citizens for Responsible Energy Solutions Forum (CRES Forum) published a policy paper that gave five recommendations on ways to modernize the U.S. electric power grid. These recommendations are to streamline the federal permit process for advanced energy projects; encourage grid planners to consider alternatives to investment in transmission; allow energy storage and energy efficiency to compete with additional energy generation; allow large customers to choose their own sources of electricity; and allow utilities and consumers to benefit from cloud computing software.[16]

See also[]

References[]

  1. ^ Jump up to: a b When the Grid Was the Grid:The History of North America’s Brief Coast-to-Coast Interconnected Machine -By JULIE COHN
  2. ^ ANSI C84.1: American National Standard for Electric Power Systems and Equipment—Voltage Ratings (60 Hertz) Archived July 27, 2007, at the Wayback Machine, NEMA (costs $83 for access)
  3. ^ CSA CAN3-C235-83: Preferred Voltage Levels for AC Systems, 0 to 50 000 V
  4. ^ Borberly, A. and Kreider, J. F. (2001). Distributed Generation: The Power Paradigm for the New Millennium. CRC Press, Boca Raton, Florida. 400 pgs.
  5. ^ Mazer, A. (2007). Electric Power Planning for Regulated and Deregulated Markets. John Wiley and Sons. Hoboken, NJ.
  6. ^ . (2001). Glover J. D., Sarma M. S., Overbye T. J. (2010) Power System and Analysis 5th Edition. Cengage Learning. Pg 10.
  7. ^ Gorman, Siobhan (2009-04-08). "Electricity Grid in U.S. Penetrated By Spies" (PDF). The Wall Street Journal. Retrieved 2018-05-02.
  8. ^ FERC:Electric Power Markets: National Overview
  9. ^ http://www.nerc.com/
  10. ^ Jump up to: a b c High-Temp Superconductors To Connect Power Grids
  11. ^ "Connecting the Grid: DC Ties Serve Critical Role". www.nmppenergy.org. NMPP Energy (Nebraska Municipal Power Pool). 2020-09-01. Retrieved 2020-12-07. HVDC ties in: Miles City, MT; Rapid City, SD; Stegall, NE; Sidney, NE; Lamar, CO; Clovis, NM; Artesia, NM
  12. ^ Billy J. Robert: U.S. Transmission System and B2B HVDC Ties, NREL, 2017-01-12
  13. ^ Visualizing The U.S. Electric Grid
  14. ^ "Control Area Concepts and Obligations" (PDF). North American Electric Reliability Council. July 1992. Archived from the original (PDF) on January 2, 2011. Retrieved July 18, 2011. Today, in NERC, there are four major interconnected areas: the Eastern Interconnection, the Western Interconnection, the Texas Interconnection, and the Québec Interconnection.
  15. ^ Jump up to: a b "Nearly three quarters of US took steps toward grid modernization in first quarter, study finds". Daily Energy Insider. 2017-05-25. Archived from the original on 2018-05-08. Retrieved 2017-06-05.
  16. ^ "Five ways to modernize the U.S. electric power grid via Advanced Energy Economy | Solar Builder". Solar Builder Magazine. 2018-08-06. Retrieved 2018-08-30.
Retrieved from ""